Analog Value Processing
Representation of Measured Value for the New PT100 Climatic Measuring Range of the 460-
7LA13 AI
Table 10.24 Representation of Digitized Measured Values for the PT100
Units
PT100/
°C
ohm
>4095
140
+4095
139.99
103.74
+2049
120.01
51.61
+2048
120
51.580
+1
100.01
0.026
0
100
0
-1
99.99
-0.026
-2048
80
-50.780
-2049
79.99
-50.81
-4095
60.01
-100.60
<-4095
60
-4095
x
-4095
x
T: Active F: Error bit OV: Overflow X: Any
1)
Only with wire break detection activated
Error bit = 1 only in case of faulty channel;
In case of transducer break overflow bit = 1 for all channels
2)
Through the PT100 series connection, this bit combination is set for all channels in the case of a break in the supply
circuit.
10-46
Climatic Measuring Range of the 460-7LA13 AI
mV at
mV com-
PT100
pensated
15 14 13 12 11 10 9 8 7 6 5 4 3
350
100
0
349.976
99.976
0
300.024
50.024
0
300
50
0
250.024
0.024
0
250
0
0
249.976
-0.024
1
200
-50
1
199.976
-50.024
1
150.024
-99.976
1
150
-100
1
Wire break
x
0
-250
1
x
0
-250
1
Digitized Measured Value
1 1 1 1 1 1 1 1 1 1 1 1 0 0 1 Overflow
1 1 1 1 1 1 1 1 1 1 1 1
1 0 0 0 0 0 0 0 0 0 0 1
1 0 0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0 0 1
0 0 0 0 0 0 0 0 0 0 0 0
1 1 1 1 1 1 1 1 1 1 1 1
1 0 0 0 0 0 0 0 0 0 0 0
0 1 1 1 1 1 1 1 1 1 1 1
0 0 0 0 0 0 0 0 0 0 0 1
0 0 0 0 0 0 0 0 0 0 0 1 0 0 1 Overflow
0 0 0 0 0 0 0 0 0 0 0 1 0 0 1 Wire break
0 0 0 0 0 0 0 0 0 0 0 1 0 1 1 Wire break
S5-115U Manual
T F OV
Range
2 1 0
Overrange
0 0 0
0 0 0
Nominal
0 0 0
range
0 0 0
0 0 0
0 0 0
0 0 0
Overrange
0 0 0
0 0 0
2)
I
/I
C+
c-
transducer
measuring
1)
circuit
EWA 4NEB 811 6130-02b