Siemens SIMATIC S5-115U User Manual page 532

Simatic s5 series cpu 941-7ub11 cpu 942-7ub11 cpu 943-7ub11 and cpu 943-7ub21 cpu 944-7ub11 and cpu 944-7ub21
Table of Contents

Advertisement

Technical Specifications
Notes for the machine manufacturer
The SIMATIC automation system is not a machine in the sense of the EC Directives Machines.
Therefore a declaration of conformity with regard to the EC Directive Machines 89/392/EC does
not exist for SIMATIC.
The EC Directive Machines 89/392/EC regulates the requirements on a machine. A machine in this
sense is a group of interconnected parts or devices (see also EN 292-1, § 3.1).
The SIMATIC is part of the electrical equipment of a machine and must therefore be included in
the declaration of conformity procedure by the machine manufacturer.
The standard EN 60204-1 (safety of machines, general requirements for the electrical equipment
of machines) applies for the electrical equipment of machines.
The following table is intended to help you with the declaration of conformity and shows which
criteria apply to SIMATIC in accordance with EN 60204-1 (June 1993).
EN 60204-1
§ 4
General requirements
§ 11.2
Digital input/output interfaces
§ 12.3
Programmable equipment
§ 20.4
Voltage tests
15-2
Topic/criterion
Remarks
Requirements are fulfilled if the devices
are assembled/installed in accordance
with the Installation Guidelines.
Please also observe the section on CE
marking.
Requirements are fulfilled.
Requirements are fulfilled if the devices
are installed in lockable cabinets to
protect them from memory
modifications through unauthorized
persons.
Requirements are fulfilled.