Siemens SIMATIC S5-100U System Manual page 457

Simatic s5 series cpu 100/102/103
Hide thumbs Also See for SIMATIC S5-100U:
Table of Contents

Advertisement

S5-100U
Function
The S5-100U programmable controller offers different solutions for individual closed-loop control
tasks. First there is a software solution for CPU 103, version 8MA02 and higher, via function blocks.
Second, there is a control module solution (for example, a module that can solve PID control tasks
simply and in a time saving manner). The basis, in both cases, is a PID control algorithm.
The closed-loop control module IP 262 can be used with the S5-90U, S5-95U, and S5-100U
programmable controllers. It can be used without COM software.
The module relieves the programmable controller from closed-loop control tasks. The IP 262 also
works with its own power supply in a stand-alone operation. The module can function independently
without a programmable controller and can handle up to four closed-loop control circuits.
Two interfaces are located on the front panel of the module.
An interface for the connection of a programmer (PG) or an operator panel (OP) or the
SINEC L1 Network (under development)
An interface for the connection of analog and binary inputs
In addition, the following items are available:
A selector switch for each channel for current and voltage (thermocouples or PT 100)
A status LED for RUN (a continuously lit green light), transducer malfunction (blinking light), and
module malfunction (off)
The module is well suited to take over control-loop tasks in the area of industrial processing
technology, for example, temperature control, pressure and flow control, continuous injection
functions, and non-time-critical closed-loop rpm controls.
Modules
There are two IP 262 modules.
... - 8MA12 with 3 analog outputs for continuous controllers with analog output signals
... - 8MB12 with 8 binary outputs for continuous controllers with pulse time-interval signals or for
step-action controllers
Additionally, the module provides the following inputs:
4 analog inputs for direct feed of setpoint and actual values
4 binary inputs for control variables
Installation
The closed-loop control module is plugged into a bus unit like any other input or output module
(see chapter 3).
The module can only be plugged into slots 0 to 7.
The connections for power supply and the analog and binary output signals are located on the
terminal block of the bus unit.
The analog and binary inputs are connected to the module with a 25-pin sub-D female
connector.
EWA 4NEB 812 6120-02b
Function Modules
15-43