S5-100U
Time-Controlled Program Processing
Access to the interrupt PII is expressed by the "PB" or "PW" operand identifiers in a statement in
the time-controlled program.
The letter "L" represents the "Load" operation (see chapter 8).
Byte-by-byte reading "PB <byte address>"
Example: Reading in the signal states of all
channels of an 8-channel digital input module
in slot 21
L PY 21
15
ACCU 1
High byte
Word-by-word reading "PW <word address>"
Example: Reading in the analog value of
channel 2 of a 4-channel analog input module
in slot 1
L PW 76
15
ACCU 1
High byte
Interrupt-Driven Program Processing
When a process interrupt occurs, only the data of the interrupt inputs, slots 0 and 1, is read into
the interrupt PII.
Only this data of the interrupt PII is available to the interrrupt-driven program for evaluation.
In a statement in the interrrupt-driven program, access to the interrupt PII is possible only with
the following operands: PB0, PB1, and PW0.
If other parameters are specified, the CPU goes into the STOP mode and the "NNN" error
message is specified in the ISTACK. See section 5.2.
EWA 4NEB 812 6120-02b
0
Low byte
0
Low byte
Figure 6-10. Accesses to the Interrupt PII
Interrupt PII
Byte 21
Byte 76
Byte 77
Addressing
6-13