Siemens SIMATIC S5-100U System Manual page 285

Simatic s5 series cpu 100/102/103
Hide thumbs Also See for SIMATIC S5-100U:
Table of Contents

Advertisement

S5-100U
Table 11-9. Analog Input Module 464-8MF21, 2x PT 100 "with Linearization" (Bipolar)
Temperature in
Resis-
Units
tance in
>1766
>400
>883
1766
1702
1700
390.26
1400
345.13
1000
280.90
600
212.02
300
157.31
200
138.50
2
100.39
0
100.00
-40
92.16
-80
84.27
-200
60.25
-202
-494
<-494
<-247
*
In the overrange area, the current slope of the characteristic curve is maintained when leaving the linearized nominal range.
EWA 4NEB 812 6120-02b
High Byte
° C
° F
>1531
0 0 1 1 0 1 1 1 0 0 1 1 0 0 0 1 Overflow
883
1531
0
0
1
1
851
1564
0
0
1
1
850
1562
0 0 1 1 0 1 0 1 0 0 1 0 0 0 0 0
700
1292
0 0 1 0 1 0 1 1 1 1 0 0 0 0 0 0
500
932
0 0 0 1 1 1 1 1 0 1 0 0 0 0 0 0
300
572
0 0 0 1 0 0 1 0 1 1 0 0 0 0 0 0
150
302
0 0 0 0 1 0 0 1 0 1 1 0 0 0 0 0
0 0 0 0 0 1 1 0 0 1 0 0 0 0 0 0 Nominal range
100
212
1
34
0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0
0
32
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
-20
-4
1 1 1 1 1 1 1 0 1 1 0 0 0 0 0 0
-40
-40
1 1 1 1 1 1 0 1 1 0 0 0 0 0 0 0
-100
-148
1 1 1 1 1 0 0 1 1 1 0 0 0 0 0 0
-101
-150
1
1
1
1
-247
-413
1
1
1
1
<-403
1 1 1 1 0 0 0 0 1 0 0 1 0 0 0 1 Overflow
Analog Value Processing
Low Byte
0
1
1
1
0
0
1
1
0
0
0
1
0
1
0
0
1
1
0
0
1
0
0
1
1
0
1
1
0
0
0
0
0
0
1
0
0
1
0
0
Range
*
0
1
Overrange
0
1
*
0
1
Overrange
0
1
11-13

Hide quick links:

Advertisement

Table of Contents
loading