Further Reduction in the Execution Time in Normal Mode
Logic operations executed in one input byte, output byte, or flag byte require only 2 µs per logic
operation. Program your control according to example 2.
Example 1:
STL
A
I
0.0
AN
I
1.1
ON
I
2.3
O
I
3.5
=
Q
4.2
A
F
15.1
A
F
16.3
AN
F
17.7
=
Q
4.5
Execution time
Approx. 6 µs/binary operation
EWA 4NEB 812 6120-02b
Example 2:
Time/ µs
5
A
6
AN
6
ON
6
O
8
=
5
A
6
A
6
AN
8
=
56 µs
Execution time
Approx. 4 µs/binary operation
Introduction to STEP 5
Time/ µs
STL
5
I
0.0
2
I
0.1
2
I
0.3
2
I
0.5
8
Q
4.2
5
F
15.1
2
F
15.3
2
F
15.7
8
Q
4.5
36 µs