Siemens SIMATIC S5-100U System Manual page 35

Simatic s5 series cpu 100/102/103
Hide thumbs Also See for SIMATIC S5-100U:
Table of Contents

Advertisement

S5-100U
Examples:
a) CPU 100:
This CPU lets you operate six digital modules (8-channel) and two analog modules
(4-channel):
[6 x 8+2 x (4 x 16)]=48+128<256
b) CPU 100:
This CPU does not let you use three digital modules (8-channel) with three analog
modules (4-channel) because the maximum permissible number of analog data bits
would be exceeded:
[3 x 8+3 x (4 x 16)]=24+192<256
c) CPU 102:
This CPU lets you operate seven digital modules (8-channel) and four analog
modules (4-channel):
[7 x 8+4 x (4 x 16)]=56+256<480
d) CPU 102:
This CPU does not let you use 20 digital modules (8-channel) with 5 analog
modules (4-channel) because the maximum permissible number of analog data bits
would be exceeded:
[20 x 8+5 x (4 x 16)]=160+320=480
e) CPU 103:
This CPU lets you operate 24 digital modules (8-channel) and eight analog modules
(4-channel):
[24 x 8+8 x (4 x 16)]=192+512=704
f)
CPU 103:
This CPU does not let you use 31 digital modules (8-channel) with four analog
modules (2-channel) because the maximum permissible number of slots would be
exceeded:
[31 x 8+4 x (2 x 16)]=248+128<704