Siemens SIMATIC S5-100U System Manual page 432

Simatic s5 series cpu 100/102/103
Hide thumbs Also See for SIMATIC S5-100U:
Table of Contents

Advertisement

Function Modules
Technical Specifications
Operating mode
(switch-selectable)
- position decoder
- counter
Sensor inputs
Digital inputs
Digital outputs
Galvanic isolation
Counting range
Operating mode
- position decoder
- counter
Counting mode
- position decoder
- counter
Setpoint input
5-V Sensor Input
Input signals
- position decoder
- counter
Counting frequency
max. 500 kHz
Cable length (shielded)
max. 50 m (165 ft.)
Power supply for decoder
Output current
max. 300 mA, short-circuit-
24-V Sensor Input
Rated input voltage
Input signals
- position decoder
- counter
Input voltage
- "0" signal
- "1" signal
Rated input current
for "1" signal
typ.
Counting frequency
max. 25 kHz
Cable length (shielded)
max. 100 m (330 ft.)
15-18
PD
C
1 sensor 5 V
(differential input) or
1 sensor 24 V DC
2; reference and
enabling
2; setpoints reached 1
and 2
no
two's complement
(KF) - 32768 to
+32767
unipolar representation
(KH) 0 to 65535
up/down
up
via program
15-pin Cannon sub-
miniature D connector
differential signals
to RS 422
A A-N, B B-N, R R-N
A A-N
5 V from L+via voltage
transformer
proof
15-pin Cannon sub-
miniature D connector
24 V DC
A, B, R
A
- 33 to 5 V DC
+13 to 33 V DC
8.5 mA
Power supply for sensor
Output current
max.
Digital Inputs
Rated input voltage
Input voltage
- "0" signal
- "1" signal
Rated input current for
"1" signal and at 24 V
typ.
Input frequency
max.
Inherent delay
typ.
Cable length (unshielded) max.
Digital Outputs
Output current
(resistive, inductive load)
Residual current for
"0" signal
max.
Switching current
for lamps
Limitation of inductive
to
interrupting voltage
Output voltage
- "1" signal
min.
- "0" signal
max.
Cable length (unshielded) max.
Short-circuit protection
(cable impedance up to 15 )
Short-circuit indication
(short-circuit to M)
Supply voltage L+
- rated value
- ripple V
max.
pp
- permissible range
(including ripple)
Fuse (internal)
Current consumption
- from L+
without sensor supply
without load
- internal (+9 V)
Power consumption
of the module
typ.
Weight
approx. 250 g (9 oz.)
S5-100U
24 V from L+
(PTC thermistor)
300 mA, short-
circuit proof
reference and
enabling
24 V DC
- 33 to +5 V DC
+13 to 33 V DC
8.5 mA
100 Hz
3 ms (1.4 to 5 ms)
100 m (330 ft.)
setpoints 1 and 2
5 mA to 0.5 A
0.5 mA
0.22 A (5 W)
-15 V
L+ - 2.2 V
3 V
100 m (330 ft.)
electronic
red LED
24 V DC
3.6 V
20 to 30 V DC
T 5 A (slow blow)
30 mA
70 mA
1.9 W+total output
current (I
)×1.1 V
A
EWA 4NEB 812 6120-02b

Hide quick links:

Advertisement