Module Spectrum
Digital Input Module 4 × 115 V AC
L1
1
N
2
3
.0
.4
4
5
.1
.5
6
7
.2
.6
8
9
.3
.7
10
2
DIGITAL INPUT
4 x 115 V AC
6ES5 430-8MC11
1
2
3
4
5
6
1
3
5
2
4
6
L1
N X.0
X.1
14-20
+9 V
GND
Data
7
9
8
10
X.2
X.3
Technical specifications
Number of inputs
Galvanic isolation
- in groups of
Input voltage L1
- rated value
- "0" signal
- "1" signal
- frequency
Input current at "1"
signal
typ.
typ.
Inherent delay
- from "0" to "1"
typ.
- from "1" to "0"
typ.
Length of cable
- unshielded
max.
Insulation rating
Rated insulation voltage
(+9 V to L1)
- insulation group
- tested with
Rated insulation voltage
(+9 V to
)
- insulation group
- tested with
Permissible ambient
temperature of module
- horizontal arrangement
- vertical arrangement
Connection of 2-wire
BERO proximity switches
- residual current
Current consumption
- from +9 V (CPU)
typ.
Power loss
of the module
typ.
Weight
approx.
S5-100U
(6ES5 430-8MC11)
4
yes (optocoupler)
4
115 V AC/DC
0 to 40 V
85 to 135 V
47 to 63 Hz
14 mA at 115 V AC
6 mA at 115 V DC
10 ms
20 ms
100 m (330 ft.)
VDE 0160
125 V AC
2×B
1250 V AC
12 V AC
1×B
500 V AC
0 to 60 °C
(32 to 140 °F)
0 to 40 °C
(32 to 104 °F)
possible
5 mA
16 mA
2.8 W
210 g (7.4 oz.)
EWA 4NEB 812 6120-02b