Module Spectrum
Digital Input Module 8 × 230 V AC
1
2
4
.0
3
.1
6
.2
5
.3
8
.4
7
.5
10
.6
9
.7
DIGITAL INPUT
8 x 230 V AC
6ES5 431-8MD11
1
2
3
4
5
6
1
3
5
2
4
6
N
L1
X.1 X.0 X.3 X.2 X.5 X.4 X.7 X.6
14-24
L1
N
2
+9 V
GND
Data
7
9
8
10
Technical specifications
Number of inputs
Galvanic isolation
- in groups of
Input voltage L1
- rated value
- "0" signal
- "1" signal
- frequency
Input current at "1"
signal
typ.
typ.
Inherent delay
- from "0" to "1"
typ.
- from "1" to "0"
typ.
Length of cable
- unshielded
max.
Insulation rating
Rated insulation voltage
(+9 V to L1)
- insulation group
- tested with
Rated insulation voltage
(+9 V to
)
- insulation group
- tested with
Permissible ambient
temperature of module
- horizontal arrangement
- vertical arrangement
Connection of 2-wire
BERO proximity switches
- residual current
Current consumption
- from +9 V (CPU)
typ.
Power loss
of the module
typ.
Weight
approx.
S5-100U
(6ES5 431-8MD11)
8
yes (optocoupler)
8
230 V AC/DC
0 to 95 V
195 to 253 V
47 to 63 Hz
16 mA at 230 V AC
1.8 mA at 230 V DC
10 ms
20 ms
100 m (330 ft.)
VDE 0160
250 V AC
2×B
1500 V AC
12 V AC
1×B
500 V AC
0 to 60 °C
(32 to 140 °F)
0 to 40 °C
(32 to 104 °F)
possible
5 mA
32 mA
3.6 W
260 g (9 oz.)
EWA 4NEB 812 6120-02b