Connection Of Resistance Thermometers - Siemens SIMATIC S5-100U System Manual

Simatic s5 series cpu 100/102/103
Hide thumbs Also See for SIMATIC S5-100U:
Table of Contents

Advertisement

Analog Value Processing
11.2.5

Connection of Resistance Thermometers

Analog input module 464-8MF11/8MF21 is suited for the connection of resistance thermometers
(e.g., PT 100).
The resistance of the PT 100 is measured in a four-wire circuit. A constant current is supplied to
the resistance thermometer via terminals 7 and 8 as well as via terminals 9 and 10, so that voltage
drops in these "constant current circuits" do not affect the measurement results. The measuring
inputs have a high resistance so that only a negligible current loss develops in the measuring
circuits.
1
2
Figure 11-7. Wiring Method for PT 100 (6ES5 464-8MF11/8MF21)
If you use only one channel for PT 100 measurement (e.g., channel 0), then you can use the other
channel for voltage measurement (± 500 mV). In this case, use terminals M+/M- for the signal
connection and short circuit the terminals I
Figure 11-8. Wiring Possibilities for Input Modules (6ES5 464-8MF11)
11-6
M0
M1
I
0
I
1
+
+
C
+
C
+
3
5
7
9
4
6
8
10
and I
C+
C-
1
3
5
2
4
6
+
-
+
V
V
Terminal assignments:
(3/4):
(5/6):
(7/8):
(9/10):
.
7
9
8
10
-
S5-100U
Measuring circuit M0
Measuring circuits M1
Constant current circuit I
0
C
Constant current circuit I
1
C
EWA 4NEB 812 6120-02b

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents