Siemens SIMATIC S5-100U System Manual page 382

Simatic s5 series cpu 100/102/103
Hide thumbs Also See for SIMATIC S5-100U:
Table of Contents

Advertisement

Module Spectrum
Digital Output Module 4 × 115 to 230 V AC/1 A
L1
1
F
N
2
3
.0
.4
4
5
.1
.5
6
7
.2
.6
8
9
.3
.7
10
FF
10A
DIGITAL OUTPUT
4x115/230V AC/1A
6ES5 450-8MD11
1
2
3 4
5
6
1
3
5
2
4
6
L1
N
X.0
X.1
X.2
14-30
3
+9 V
GND
Data
7
9
8
10
X.3
Technical specifications
Number of outputs
Galvanic isolation
- in groups of
Load voltage L1
- rated value
- frequency
max. 47 to 63 Hz
- permissible range
Output current for
"1"signal
- rated value
- permissible range
- lamp load
max. 25/50 W
Contact current closing
rating:
Residual current at
"0" signal
max. 3/5 mA
Output voltage
- "1" signal
max. L1 (- 7 V)
Signal status display
(green LEDs)
Short-circuit protection
Fault LED (red)
Switching frequency
max. 10 Hz
Permissible current
of all outputs
Driving of digital input
Paralleling of outputs
Permissible ambient
temperature of module
- horizontal arrangement
- vertical arrangement
Length of cable
- unshielded
max. 100 m (330 ft.)
Insulation rating
Rated insulation voltage
(+9 V to L1)
- insulation group
- tested with
Rated insulation voltage
(+9 V to
)
- insulation group
- tested with
Current consumption
- from +9 V (CPU)
typ.
Power loss of the
module
typ.
Weight
approx. 315 g (11 oz.)
* Indication only given if load voltage is
applied and at least one load is connected
S5-100U
(6ES5 450-8MD11)
4
yes
4
115 to 230 V AC
85 to 264 V
1 A
50 mA to 1 A
determined by the
size of the fuse
only with load
connected
fuse
(10 A extra fast)
(Wickmann No.
19231, or
6ES5 980-3BC41)
fuse blown *
4 A
possible
not possible
0 to 60 °C
(32 to 140 °F)
0 to 40 °C
(32 to 104 °F)
VDE 0160
250 V AC
2×B
1500 V AC
12 V AC
1×B
500 V AC
14 mA
3.5 W
EWA 4NEB 812 6120-02b

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents