No. Cd: Read_And_Delete_As-I_Slave_Error_Counter - Siemens SIMATIC ET 200SP Manual

As-interface master cm as-i master st 3rk7137-6sa00-0bc1
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Byte
16
Summation counter: Sent master frames, more significant part (MT_CNT_HIGH)
17
18
19
20
Summation counter: Sent master frames, factor (MT_CNT_BASE)
21
22
23
24 ... 31
9.4.36

No. CD: Read_and_delete_AS-i_Slave_error_counter

Note
With Firmware V1.1 or higher, use data records "DS 150 to DS 153 Read AS-i error counters
(Page 89)" and "DS 154 Delete AS-i error counters (from FW V1.1) (Page 96)". The
Read_and_Reset_AS-i_Slave_Error_Counters command continues to exist for compatibility
reasons.
Meaning
This command reads out the error counters of the AS-i slaves. Data records DS 150 and
DS 151 access the standard addresses and the A addresses. Data records DS 152 and
DS 153 access the B addresses. The counters for addresses 16 / 16A exist identically in
data records DS 150 and DS 151. The counters for address 16B exist identically in data
records DS 152 and DS 153. Data record DS 154 resets all AS-i slave error counters.
Structure of the job data in the send buffer
Table 9- 68
Structure of the job data in the send buffer
Byte
0
1
Structure of the responses in the receive buffer
The receive buffer is identical to the receive buffer of the "No. CC: Read_AS-i_error_counter
(Page 156)" command.
AS-Interface master CM AS-i Master ST (3RK7137-6SA00-0BC1)
Manual, 07/2017, A5E02655262020A/RS-AD/004
Meaning
Reserved
Meaning
Command number: CD
H
AS-i slave address
Using the command interface
9.4 Description of the AS-i commands
High word / high byte
High word / low byte
Low word / high byte
Low word / low byte
High word / high byte
High word / low byte
Low word / high byte
Low word / low byte
157