Using the command interface
9.3 Command interface with controllers of other manufacturers
Return value
Processing errors are itemized in the return value of the response buffer, if necessary. An
error indication exists when "ended without error and without response data or ended with
error" is displayed in the status nibble (coding: 0001
Table 9- 2
Return value in the response buffer
STATUS
0000
Job completed without errors
H
8381
The AS-i slave address is incorrect.
H
8382
The AS-i slave is not activated (not in LAS).
H
8383
Error on the AS-Interface
H
8384
The command is not permitted in the current state of the AS-i master.
H
8385
An AS-i slave with address 0 exists.
H
8386
The AS-i slave has impermissible configuration data (IO, ID, ID2, or ID1 code).
H
83A1
The referenced AS-i slave was not found on the AS-Interface.
H
83A2
An AS-i slave with address 0 exists.
H
83A3
An AS-i slave with the new address already exists on the AS-Interface.
H
83A4
The AS-i slave address cannot be deleted.
H
83A5
The AS-i slave address cannot be set.
H
83A6
The AS-i slave address cannot be permanently saved.
H
83A7
Error while reading the ID1 code
H
83A8
The destination address is not plausible: e.g. a B slave address is used for a standard slave.
H
83B1
A length error occurred during the string transfer in accordance with Profile 7.4.
H
83B2
A protocol error occurred during the string transfer in accordance with Profile 7.4.
H
83C0
The AS-i slave has an invalid profile, e.g. the standard slave or A slave is configured at a B address.
H
83C1
The standard slave cannot be configured, because the B address is already assigned.
H
83F8
The job number or the job parameter is not known.
H
83F9
The AS-i master has detected an EEPROM error.
H
Note
Errors that occur during processing of acyclic services and are reported via call parameters,
such as "Return Value", can be found in the documentation of the relevant programming
interface.