Channel /
Fault
Fault type
No.
Message
0402
1026
Peripheral fault in AS-i slave
H
0403
1027
Peripheral fault in AS-i slave on
H
B address
0404
1028
AS-i address used multiple times Multiple AS-i slaves with the same
H
0405
1029
AS-i B address used multiple
H
times
AS-Interface master CM AS-i Master ST (3RK7137-6SA00-0BC1)
Manual, 07/2017, A5E02655262020A/RS-AD/004
Cause
An AS-i slave on an A address or a
slave with a standard address signals
a peripheral fault. The channel number
of the message shows the address of
the affected AS-i slave.
Possible cause:
An overload at the output of a
digital slave or an overload at the
actuator
Measuring range exceeded for
analog input slaves
Overload of the sensor supply at
the input slave (only for some slave
types)
Group fault message for M200D
motor starters
An AS-i slave on a "B" address signals
a peripheral fault. The channel number
of the message shows the address of
the affected AS-i slave.
Possible cause:
An overload at the output of a
digital slave or an overload at the
actuator
Measuring range exceeded for
analog input slaves
Overload of the sensor supply at
the input slave (only for some slave
types)
Group fault message for M200D
motor starters
profile and address are located on the
AS-i bus. The affected slaves have a
standard address or A address. The
channel number of the message
shows the address of the affected
AS-i slave.
Multiple AS-i slaves with the same
profile and address are located on the
AS-i bus. The affected slaves have a B
address. The channel number of the
message shows the address of the
affected AS-i slave.
Alarms, faults and system events
8.4 Diagnostic messages
Remedial measures
Note the information in the
manual for the AS-i slave.
Check:
Slave
Overload
Connected sensors
and actuators
Note the information in the
manual for the AS-i slave.
Check:
Slave
Overload
Connected sensors
and actuators
Change the addresses of
the AS-i slaves to
addresses that are unique
in the network.
Change the addresses of
the AS-i slaves to
addresses that are unique
in the network.
71