Alarms, faults and system events
8.6 Duplicate address detection
Function description
The duplicate address detection function assists you in identifying inadvertent duplicate
addressing.
When commissioning the AS-i system, check that duplicate address detection can be used
for the AS-i configuration used.
● Install the complete AS-i system and ensure that the specified addresses of the slaves
are correct and unique.
● Enable the duplicate address detection function. In firmware V1.1 and higher, you can do
this for AS-i voltages of either 24 V or 30 V.
● Check whether the CM AS-i Master ST signals a duplicate address in spite of correct
slave address assignment. If a duplicate address is signaled on the AS-i master even
though the bus configuration is correct, this means that duplicate address detection
cannot be used for this bus configuration. Should this occur, disable the duplicate
address detection function.
● Note that when the duplicate address detection function is enabled, the presence of a
duplicate address may not be detected, depending on the bus configuration.
Note
The activation status is saved in volatile memory of the AS-i master. After a startup or restart
of the CM AS-i Master ST, duplicate address detection must be activated again via the user
program, if required.
The CM AS-i Master ST signals a detected duplicate address as follows:
● The "CER" LED lights up to indicate a configuration error.
● The "SL_Xy (A)" and "SL_xY (B)" LEDs signal the AS-i address concerned.
● The message "AS-i address used multiple times" is output.
To rectify the fault, check and change the address of the affected AS-i slave, e.g. using the
addressing unit. Via the online function of
AS-i address of an individual slave if there are multiple slaves with the same address on the
AS-i cable.
See also
DS 100 Read setting for duplicate address detection (Page 172)
78
STEP 7
it is not possible to change the
AS-Interface master CM AS-i Master ST (3RK7137-6SA00-0BC1)
Manual, 07/2017, A5E02655262020A/RS-AD/004