No. Cb: Read_And_Delete_As-I-Master_Error_Counter - Siemens SIMATIC ET 200SP Manual

As-interface master cm as-i master st 3rk7137-6sa00-0bc1
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

9.4.34

No. CB: Read_and_Delete_AS-i-Master_Error_Counter

Note
With Firmware V1.1 or higher, use data record "DS 97 Read and reset AS-i master error
counters (FW V1.1 and higher) (Page 89)" for reading out the error counters. The
Read_and_Reset_AS-i_Master_Error_Counters command continues to exist for compatibility
reasons.
Meaning
This command functions like the "Read_AS-i-Master_Error_Counter" command. In addition,
the AS-i master then sets all error counters to 0.
Structure of the job data in the send buffer
Table 9- 65
Structure of the job data in the send buffer
Byte
0
Structure of the responses in the receive buffer
The receive buffer is identical to the receive buffer of the "No. CA: Read_Error_Counter
(Page 152)" command.
AS-Interface master CM AS-i Master ST (3RK7137-6SA00-0BC1)
Manual, 07/2017, A5E02655262020A/RS-AD/004
Meaning
Command number: CB
H
Using the command interface
9.4 Description of the AS-i commands
155

Advertisement

Table of Contents
loading

Table of Contents