Table of Contents

Advertisement

4. The detected slaves are applied as universal slaves in the project.
Note
Automatic reading out of article numbers is not possible.
Slave addresses already present in the project are not overwritten. If you want to transfer
a slave address that is already present, you must delete the existing slave in the
hardware detection before the readout.
5. You can now edit the slaves applied to the project as if you had taken them directly from
the hardware catalog.
The following basic types are available:
● Siemens AS-i slave
● Universal slave with the following forms:
– AS-i F Slave Universal for safety-related applications
– AS-i Standard Slave Universal, for configuring with standard address or extended
– Universal AS-i Proxy Slave
The article numbers for the slaves are only saved in the offline project. Comparison of the
article numbers in the offline project with those of the slaves on the AS-i cable is not
performed. The AS-i master uses the configuration data of the slave profile (IO.ID.ID2) and
ID1 code of the AS-i slave for comparison of the actual status with the configured status.
Configuring the properties of Siemens AS-i slaves
When you use an AS-i slave from Siemens, you select the slave directly from the hardware
catalog.
This selection offers the following properties:
● The device type is represented in
● The meaning of the slave parameters is displayed as text.
● The underlying slave profile is already set. The IO, ID and ID2 identifiers do not need to
be entered.
Parameter bits that are irrelevant for the Siemens slave are set to the default value "1". They
cannot be changed.
The ID1 code is preassigned according to the factory setting of the Siemens slave. If you
change the ID1 code of the slave, you must also change the setting in the slave
configuration.
See also the command "No. D1: AS-i-Slave_ID1_schreiben_mit_Zieladresse (Write ID1 code
with destination address) (Page 160)".
AS-Interface master CM AS-i Master ST (3RK7137-6SA00-0BC1)
Manual, 07/2017, A5E02655262020A/RS-AD/004
address (A/B slaves)
5.3 Configuration of the AS-i slaves
STEP 7
(TIA Portal) using an image.
Configuring
33