Siemens SIMATIC ET 200SP Manual page 73

As-interface master cm as-i master st 3rk7137-6sa00-0bc1
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Channel /
Fault
Fault type
No.
Message
040C
1036
Incorrect AS-i slave
H
040D
1037
Incorrect AS-i slave at B address There is an incorrect AS-i slave with a
H
AS-Interface master CM AS-i Master ST (3RK7137-6SA00-0BC1)
Manual, 07/2017, A5E02655262020A/RS-AD/004
Cause
On the AS-i bus there is an incorrect
AS-i slave with a default address or an
A address. The channel number of the
message shows the address of the
AS-i slave involved.
B address on the AS-i bus. The
channel number indicates the B
address of the affected slave.
Alarms, faults and system events
8.4 Diagnostic messages
Remedial measures
Use the correct slave
type.
Set the ID1 code on
the slave in
accordance with the
CONFIGURED
configuration.
Use the correct slave
type.
Set the ID1 code on
the slave in
accordance with the
CONFIGURED
configuration.
73