9.4.13

No. 0C: Set_Operation_Mode

Meaning
This command chooses between "configuration mode" and "protected operation".
In "protected operation", only the AS-i slaves that are flagged in the LPS and whose
CONFIGURED and ACTUAL configurations match are activated. This is the case when the
I/O code and the ID codes of the detected AS-i slaves are identical to the configured values.
In "configuration mode", all the detected AS-i slaves are activated - with the exception of
AS-i slave "0". This also applies to AS-i slaves that differ in their CONFIGURED and
ACTUAL configurations.
The "OPERATING MODE" bit is saved in non-volatile memory. As a result, this bit is
retained in the event of startup or restart.
On switching from "configuration mode" to "protected operation", the AS-i master restarts. It
enters the offline phase and then switches to online mode.
Note
AS-i slave with address 0 prevents switchover to "protected operation"
If an AS-i slave with address 0 is present on the AS-i bus, the AS-i master cannot switch
from "configuration mode" to "protected operation".
Structure of the job data in the send buffer
Table 9- 24
Structure of the job data in the send buffer
Byte
Bit 7
0
1
AS-Interface master CM AS-i Master ST (3RK7137-6SA00-0BC1)
Manual, 07/2017, A5E02655262020A/RS-AD/004
Bit 1
Command number: 0C
0
9.4 Description of the AS-i commands
Meaning
H
Operating mode
0 = "Protected operation"
1 = "Configuration mode"
Using the command interface
Bit 0
119