Communication Objects Heating/Cooling - ABB i-bus KNX Product Manual

Fan coil actuators fca/s
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
3.3.5.4

Communication objects Heating/Cooling

120
If a fan coil operating mode with switching object is selected in the
parameter Toggle to heating with will appear. Depending on the selection, the communication object Toggle heating decides
whether to use heating or cooling mode.
Telegram value:
121
If a fan coil operating mode with two control values and two valves is selected in
p. 76, the parameter communication object "Valve control values parallel mode" 1-bit will appear. If the option Yes is selected
for this, both valves can move the same way, e.g. both to 50%. If the communication object is switched off again, the previous
state will be restored.
Telegram value:
236 2CDC508134D0202 | FCA/S 1.x.x.1
Toggle heating
0 = Heating
1 = Cooling
Valve control values parallel mode
0 = No function
1 = Parallel mode
General
Parameter window Enable output
General
Parameter window Enable output
1 bit
C, W
DPT 1.100
A...D, p. 76, the
1 bit
C, W
DPT 1.100
A...D,