ABB i-bus
KNX
Commissioning
Value 1 (event 0 or
on short operation)
Options:
This parameter serves for defining the data type which is sent when the contact is actuated.
Note
With the setting 2-byte value (floating point), rounding off errors can occur, meaning that the value sent
to the bus may not correspond precisely to the set value. If a high degree of precision is required, select
the option 4-byte value (floating point).
Depending on the selection made in the parameter Value 1, different parameters will appear. All
parameters are described in the following:
Do not send
1-bit value [0/1]
2-bit value (forced operation)
1-byte value [-128...127]
1-byte value [0...255]
1-byte value (8-bit scene)
2-byte value [-32,768...32,767]
2-byte value [0...65,535]
2-byte value (floating point)
4-byte value (floating point)
3-byte value (time of day/weekday)
4-byte value [-2147483648...2147483647]
4-byte value [0...4294967295]
Sent value [X]
Options:
ON/OFF/TOGGLE
0/1
-128...0...127
0...255
-32,768...0...32,767
0...65,535
-100...0...100
-2147483648...0...2147483647
0...4294967295
This parameter defines the value which is sent on operation. The value range is dependent on the
set data type of the value X.
Sent value (forced operation)
Options:
ON, activate forced operation
OFF, activate forced operation
Disable forced operation
This parameter defines the value which is sent on operation.
FCA/S 1.x.x.1 | 2CDC508134D0202 187