ABB i-bus
KNX
Commissioning
No.
66
This communication object is enabled if the parameter Enable automatic operation has been selected with the option Yes in
Parameter window E, F, G: Fan
If automatic mode is enabled, it will be activated on this communication object with the value 1 after a download, ETS reset or
via a telegram. Automatic mode is switched off if a signal is received on a "manual communication object".
Manual communication objects are:
During one of the four limitations or forced operation, automatic mode remains active but operates only within the allowed
limits.
If the value 1 is set in the parameter:
Telegram value:
If the value 0 is set in the parameter:
Telegram value:
67
This communication object is enabled if the parameter Enable communication object "Status Automatic" 1-bit has been
selected with the option Yes in
You can parameterize whether the communication object value is updated but not sent, sent on request, or only sent when
changed.
The communication object indicates the status of automatic operation.
Telegram value:
Functionality
Automatic ON/OFF
(One-level), p. 149.
Fan: Switch speed
Fan: Switch speed x (x = 1, 2 or 3)
Fan: Fan speed up/down
Fan: Limitation x (x = 1, 2, 3 or 4)
0 = Automatic operation OFF
1 = Automatic operation ON
0 = Automatic operation ON
1 = Automatic operation OFF
Status Automatic
Parameter window Status messages (single
0 = Inactive
1 = Activated
communication object name
Fan E, F, G
Fan E, F, G
speed), p. 152.
Data type
Flags
1 bit
C, W
DPT 1.003
1 bit
C, R, W
DPT 1.003
FCA/S 1.x.x.1 | 2CDC508134D0202 225