ABB i-bus KNX Product Manual page 214

Fan coil actuators fca/s
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
No.
11
This communication object is enabled with the option Yes via the parameter Enable communication object "Status control
value" in
The control status of the output is sent via this communication object. Hereby, the limit position that the valve should assume
is transferred.
The object is not sent in the event of a short circuit, overload, failure of the supply voltage and reference adjustment (only in
operation mode Valve drive, motor-driven (3-point)).
The LED of the corresponding output indicates the same value as the status.
The status is sent if:
Telegram value:
11
This communication object is enabled with the option Yes via the parameter Enable communication object "Status control
value" in
The control status of the output is sent via this communication object.
The LEDs of the corresponding outputs indicates the same value as the status.
The status is sent if:
Telegram value:
212 2CDC508134D0202 | FCA/S 1.x.x.1
Functionality
Status Control value
Parameter window Function,
Note
Signaling via LED occurs only for the devices FCA/S 1.1.2.2 and FCA/S 1.2.2.2.
a request is received via the communication object Request status values and the parameter is set to After request or
After a change or request.
the value of the communication object has changed and the parameter is set to After request or After a change or
request.
a read request is carried out on this communication object.
0...255 = Control is displayed directly as a figure value
At 0 = LED (yellow) off
At > 0 = LED (yellow) on
Status Control value
Parameter window Function,
a request is received via the communication object Request status values and the parameter is set to After request or
After a change or request.
the value of the communication object has changed and the parameter is set to After request or After a change or
request.
a read request is carried out on this communication object.
0 = Control value equal to zero/LED (yellow) off
1 = Control value not equal to zero/LED (yellow) on
communication object name
Output A
Output A/B
p. 113, and with selection of the option Byte in the parameter Data type.
Output A
Output A/B
p. 113, and with selection of the option Bit in the parameter Data type.
Data type
Flags
1 byte
C, R, T
DPT 5.001
1 bit
C, R, T
DPT 1.011

Advertisement

Table of Contents
loading

Table of Contents