KNX
Commissioning
No.
18
This is a diagnostics byte for the output. The value of the communication object is sent when a telegram is received on the
communication object Request status values. The communication object is always visible.
Telegram value:
For further information see:
19
Not assigned
20...29
communication objects for output B
See communication objects 10...19, output A
30...39
communication objects for output C
See communication objects 10...19, output A
40...49
communication objects for output D
See communication objects 10...19, output A
Functionality
Status byte
Bit sequence
Bit 7:
Not assigned
Bit 6:
Not assigned
Bit 5:
Not assigned
Bit 4:
Overload/short circuit current
0:
1:
Bit 3:
Manual operation active
0:
1:
Bit 2:
Safety priority 1, 2, 3 (forced operation or block)
0:
1:
Bit 1:
Purging
0:
1:
Bit 0:
Status output/control value > 0
0:
1:
Status byte outputs A, B, C,
communication object name
Output A
Output A/B
76543210
Always 0
Always 0
Always 0
No overload/short-circuit
Overload/short circuit current
Manual operation inactive
Manual operation active
None active
At least one active
No valve purge
Valve purge active
Control value = 0 / output = OFF
Control value = 0 / output = ON
D, p. 257
Output B
Output C
Output D
Data type
Flags
1 byte
C, R, T
non DPT
FCA/S 1.x.x.1 | 2CDC508134D0202 215