Commissioning
Fan speed on bus voltage recovery
Options:
The reaction of the fan on bus voltage recovery is defined here.
Unchanged: The fan speed remains the same.
OFF: The fan is switched off.
ON: The fan is switched on.
Attention
The device is supplied ex-works with a default setting (factory default). This ensures that the fan setting
is switched off when the bus voltage is applied to the relay for the first time. Thus, damage to the device
due to unintentional switch on during transport, e.g. due to vibration, is avoided.
It is advisable to apply a bus voltage before connecting the fan in order to assign it a defined switch
state. This eliminates the possibility of an incorrect contact setting destroying the fan.
Enable automatic operation
Options:
Yes: Automatic operation is enabled. The
also appears.
Function Time on ON
Options:
This defines the Time function on Fan ON.
None: No Time function is executed.
Switching delay: The fan is switched on after this delay.
Minimum time: The fan remains ON for at least this time.
Selection of option Switching delay:
Selection of option Minimum time:
150 2CDC508134D0202 | FCA/S 1.x.x.1
Unchanged
OFF
ON
No
Yes
None
Switching delay
Minimum time
Dependent parameter:
Time in s [1...65,535 x 0.1]
1...20...65,535
Options:
The fan is switched on after this delay.
Dependent parameter:
Time in s [1...65,535]
1...20...65,535
Options:
The fan remains ON for at least this time.