Communication Objects Fan E, F, G; Communication Objects Fan Multi-Level - ABB i-bus KNX Product Manual

Fan coil actuators fca/s
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
3.3.4

Communication objects Fan E, F, G

Note
All three fan speeds can also be individually parameterized as outputs E, F and G. The descriptions of
the communication objects for this can be found under
p. 228,
The setting options are described in
3.3.4.1

Communication objects Fan Multi-level

No.
50
This communication object is enabled if the parameter Enable direct operation has been selected with the option Yes in
Parameter window E, F, G: Fan
has been selected with the option DPT 5.001 in
With this communication object, the fan can be switched on via a 1 byte communication object of a fan speed. If another fan
speed is switched on, at this point it will be switched off. The new fan speed is switched on taking the start-up phase into
consideration.
Limitations through forced operation or one of the four limitations 1...4 are retained. Automatic operation is disabled.
communication object Automatic ON/OFF reactivates automatic operation.
The thresholds set in the parameter window Thresholds that define the fan speeds 1, 2 and 3 are valid.
Telegram value:
50
This communication object is enabled if the parameter Enable direct operation has been selected with the option Yes in
Parameter window E, F, G: Fan
has been selected with the option DPT 5.010 in
With this communication object, the fan can be switched on via a 1 byte communication object of a fan speed. If another fan
speed is switched on, at this point it will be switched off. The new fan speed is switched on taking the start-up phase into
consideration.
Limitations through forced operation or one of the four limitations 1...4 are retained. Automatic operation is disabled.
communication object Automatic ON/OFF reactivates automatic operation.
The following telegram values result:
216 2CDC508134D0202 | FCA/S 1.x.x.1
communication objects Output
Functionality
Switch speed
(Multi-level), p. 124, and the parameter Enable communication object "Switch speed" 1-byte
0 =
Fan OFF
1...255 = Fan ON
Switch speed
(Multi-level), p. 124, and the parameter Enable communication object "Switch speed" 1-byte
1 byte value
Hexadecimal
0
00
1
01
2
02
3
03
>3
>03
Communication objects Switch actuators
F, p. 228 and
communication objects Output
Parameter window Enable output
communication object name
Fan E, F, G
Parameter window Direct operation
Fan E, F, G
Parameter window Direct operation
Binary value bit
76543210
00000000
0 (OFF)
00000001
Fan speed 1
00000010
Fan speed 2
00000011
Fan speed 3
>00000011
Values greater than 3 are ignored
G, p. 228.
E...H, p. 123.
Data type
Flags
1-byte
C, W
DPT 5.001
(Multi-level), p. 143.
1-byte
C, W
DPT 5.010
(Multi-level), p. 143.
Fan speed
E,