Line Fault Compensation Via Cable Length - ABB i-bus KNX Product Manual

Fan coil actuators fca/s
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
3.2.4.4.3

Line fault compensation Via cable length:

Cable length, single distance
[1...30 m]
Options:
For setting the single cable length of the connected temperature sensor.
Important
The maximum cable length permitted between the sensor and device input is 30 m.
Cross-section of conductor
Value * 0.01 mm
Options:
The cross-section of the conductor to which the temperature sensor is connected is entered using this
parameter.
Important
Line fault compensation via cable length is only suitable for copper conductors.
1...10...30
2
[1...150]
1...100...150 (150 = 1.5 mm
2
)
FCA/S 1.x.x.1 | 2CDC508134D0202 197