ABB i-bus
KNX
Commissioning
KTY user-defined
The following ohmic values must
rise to higher temperatures
<- Note
To ensure correct functioning of the Analogue Input with respect to the user-defined entries, the ohm
(resistance) values as visible for the preset values must be in ascending order.
An incorrect entry can lead to unrealistic output values!
Resistance in ohms at -50...+150 °C
Options:
A resistance characteristic can be entered via these 11 parameters. The data can be found in the sensor
manufacturer's technical documentation.
Note
The description of the further parameters can be found in the description
PT1000, p. 191.