ABB i-bus
KNX
Commissioning
Enabled: The operating states Manual operation and KNX operation can be toggled via button .
Enable/disable via communication object: The communication object Block manual operation -
General appears.
Telegram value:
Blocked: Manual operation is generally disabled
Reset from manual operation to
KNX operation
Options:
This parameter determines whether, after pressing the button , the device will remain in Manual
operation or will be reset back to KNX operation.
Yes: The device is reset to KNX operation.
0 = Enable
button
1 = Block
button
No
Yes
Dependent parameter:
Time for automatic reset
to KNX operation in s [1...65,535]
1...30...65,535
Options:
This parameter determines how long, after pressing button
operation.
The device remains in Manual operation after the last button push until either button
again or the programmed time has timed out.
, the device will remain in Manual
FCA/S 1.x.x.1 | 2CDC508134D0202 73