ABB i-bus
KNX
Commissioning
3.2.4.4.4
Line fault compensation Via cable resistance
Cable resistance in milliohms
(total of forw. and ret. conduct.)
Options:
Using this parameter the level of cable resistance of the connected temperature sensor is set.
Important
In order to correctly measure the cable resistance, the conductors must be shorted together at the end
of the cable and should not be connected to the Analogue Input.
198 2CDC508134D0202 | FCA/S 1.x.x.1
0...500...10,000