Commissioning
Enable communication object
"Status byte fan" 1-byte
Options:
From this status byte the states heating, cooling, automatic, forced operation and the four limitations are
indicated directly via a 1 bit coding.
For further information see:
Yes: The communication object Status byte fan is enabled.
132 2CDC508134D0202 | FCA/S 1.x.x.1
No
Yes
Status byte
Dependent parameter:
Send object value
Options:
No, update only
On change
After request
After a change or request
No, update only: The status is updated but not sent.
On change: The status is sent when a change occurs.
After request: The status is sent when a request occurs.
After a change or request: The status is sent on a change or a request.
fan, p. 258