Connecting Cerberus Remote - Siemens FC7xx Operation Manual

Fire control panel / fire terminal
Table of Contents

Advertisement

Operation
5

Connecting Cerberus Remote

5.20 Connecting Cerberus Remote
98 | 184
Building Technologies
Fire Safety
Cerberus-Remote can only ever be connected with one ↑ 'Station' at a time. The
connection can be established locally or via the 'Global Access Point' (GAP). For
this purpose, there must be a ↑ license key installed in the 'Station' that is to be
displayed with Cerberus-Remote. The license key must support the Cerberus-
Remote function.
Cerberus-Remote has the same ↑ visibility as the connected ↑ 'Station'. You can
use Cerberus-Remote in a fire detection installation with networked 'Stations' to
gain global visibility. Just one ↑ license key is needed for this per network if the
license key is installed in a 'Station' with global visibility.
You will find more information about ↑ license keys in document A6V10210362.
See chapter 'Applicable documents'.
The possible 'Enable full access' or 'Enable view access' operation modes must be
enabled before connecting to the ↑ 'Station'. The possible operation modes can
also be permanently enabled in the configuration with Cerberus-Engineering-Tool.
Establishing connection
1. Select 'Cerberus-Engineering-Tool' > 'Task Card 'Cerberus-Remote''.
2. Select 'Menu bar' > 'Cerberus-Remote' > 'Connect'.
 A window with the selection of the connection type is indicated.
3. Select the required type of connection and confirm with 'OK'.
 A window with the list of all 'Stations' of the 'Site' is indicated.
4. Highlight the corresponding 'Station'.
5. Enter your PIN.
6. Click on 'OK'.
 The connection is established.
The connection with a 'Station' is shown by the ↑ Person Machine Interface
(display, LEDs, keys) transmitted.
The 'Cerberus-Remote access' operation mode is indicated by a red frame
around the Person Machine Interface.
An enable granted for Cerberus-Remote is retained when a ↑ 'Station' is
restarted.
A6V10211076_i_en_--
2015-12-15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ft724