Activation / Deactivation / Reset; Activating An Alarm Indicator (Ai) - Siemens FC7xx Operation Manual

Fire control panel / fire terminal
Table of Contents

Advertisement

Operation
5

Activation / Deactivation / Reset

5.13 Activation / Deactivation / Reset

5.13.1 Activating an alarm indicator (AI)

78 | 184
Building Technologies
Fire Safety
You can activate and deactivate outputs, for example 'Sounders'.
Channel inputs, e.g. detectors, may be activated but not deactivated. These can be
reset after activation.
When 'Fire controls' is activated, this triggers smoke dampers, elevators, system
equipment, and extinguishing equipment (including those with extinguishing
gases), for example. You must take appropriate measures to prevent any possible
damage.
WARNING
Deactivated controls hinder appropriate measures in case of fire!
Personal injury and damage to property in the event of a fire.
Deploy staff to monitor the deactivated area.
You must reactivate deactivated controls as soon as possible.
WARNING
Activated parts of the system may actuate alarming and fire control!
Personal injury resulting from extinguishing activation.
The fire brigade is called up unnecessarily.
Set the 'Fire controls' to 'Control test'.' in advance.
Inform the fire brigade in advance.
You can activate an ↑ alarm indicator, e.g., to check the geographic assignment of
a detector. This function is of use for the commissioning or maintenance.
'Activate alarm indicator'
1. Select 'Main menu' > 'Topology'.
 The three partial trees of the topology tree are indicated.
2. Select 'Detection tree'.
3. Go on navigating through the tree structure to the next detector, using the
'Lower level' softkey 2.
4. Highlight a detector.
5. Press 'More Options' <softkey 3>.
 The 'Select option' window is open.
6. Select the 'Execute commands' option.
 The 'Select command' window is displayed.
7. Select the 'Activate alarm indicator' command.
 The ↑ alarm indicator is activated.
A6V10211076_i_en_--
2015-12-15

Hide quick links: