System functions
6

Isolation

6.6 Isolation

6.7 Renovation

6.8 Access level and access rights

116 | 184
Building Technologies
Fire Safety
You can ↑ switch off 'Zones' with automatic or non-automatic detectors in special
situations, e.g., during construction work.
When parts of the fire detection installation are switched off, the fire detection
installation is in 'ISOLATION' condition and operation mode.
The 'ISOLATION' LED on the Person Machine Interface is on.
In 'ISOLATION' operation mode neither 'ALARMS' nor 'Faults' from the parts of the
↑ site that have been switched off can be evaluated.
You can set isolations with or without a time limit.
See also
1 Switching off / Switching on [➙ 45]
In the ' --Renovation mode' operation mode, the detector ↑ parameter sets are
changed as follows:
No evaluation possible by the optical part of the detector.
A static evaluation by the thermal part of the detector is possible, however,
without the evaluation of the temperature difference.
The 'ISOLATION' LED on the ↑ PMI is on as soon as a part of the ↑ site has
been set to ' --Renovation mode'.
The ↑ 'Station' is protected against unauthorized operation by the following access
levels:
Access level
Access rights
1
Everybody
2,1
Operator 1
2,2
Operator 2
3
Service technician All access rights (for service technicians)
On access level 1 the most important commands can be entered in case of
alarm.
Other commands or the configuration of the ↑ 'Station' are possible starting
with access level 2,1.
Access levels are enabled by the PIN input dialog or the key switch.
Each PIN is assigned to an access level.
Menu entries, functions and favorites that are not accessible on an access level
are hidden.
You will find a list of all commands and the required access levels in the relevant
chapter.
Functions and access rights
'Acknowledge' and scrolling
Limited access rights (e.g. janitor)
Extended access rights (e.g. safety and
security manager)
A6V10211076_i_en_--