Siemens FC7xx Operation Manual page 20

Fire control panel / fire terminal
Table of Contents

Advertisement

Setup of the Person Machine Interface
3
PMI
6
Key switch (optional)
7
<Alarm device> button
8
System fault LED (yellow)
9
Operation LED (green)
A
<More alarms> button
S
Softkeys 1–3
X
<Silence buzzer>,
<Acknowledge>, <Reset>,
<Alarm delay off>, <Premises
manned> standard buttons
k1 Configurable keys with LEDs
k2 Configurable LEDs
20 | 184
Building Technologies
Fire Safety
An access level can be enabled with the key switch.
The accessible access level is configurable.
The key switch has two positions: On (horizontal position), Off
(vertical position)
Deactivates the ↑ alarm devices in the event of alarm (password
required)
Lights up yellow when a fault is present
Lights up green during operation
Pressing <More alarms> opens the 'ALARMS' event list.
If the 'ALARMS' event list is already open, <More alarms> assumes
the function of the button <▼>, changing to the next alarm event
upon activation.
Softkeys are buttons by means of which functions may be carried
out that are displayed in the three fields of the softkey line on the
display.
These three black fields contain the names of the functions in white
font.
The functions of the softkeys may change depending on the situation
and the contents of the display.
Always the most important functions are assigned to the softkeys 1
and 2.
<Silence buzzer> switches the buzzer off.
<Acknowledge> acknowledges all events that can be acknowledged.
Confirms presence (↑ AVC, IC). Switches off the buzzer and internal
sounders.
<Reset> resets all events that can be reset (password required).
<Alarm delay off> switches off the alarm delay for all events. In the
event of an alarm, the remote transmission or global alarming is
activated immediately.
<Premises manned> switches between 'Manned' and 'Unmanned'
operation modes (password required). Opens the event list in the
case of a "mixed" condition (↑ visibility on several ↑ areas with
different 'Manned' and 'Unmanned' settings).
These two keys may, for example, be configured with the following
functions: 'VdS counter' or 'Switch off detector zone' display.
Freely configurable for the indication of events or conditions
Inscription strips may be inserted to label the PMI.
You will find a template for this in document A6V10217440. See chapter
'Applicable documents'.
A6V10211076_i_en_--
2015-12-15