5.4.3 Temporary switching-off

Building Technologies
Fire Safety
Temporary switching-off is only possible at level 'Area', 'Section', 'Zone', or
'Detector'.
Override for different settings
If a detector has been temporarily isolated and its 'Zone' has been permanently
isolated, the detector is also permanently isolated.
If a detector has been temporarily isolated and its 'Zone' has been temporarily
isolated, the time limit for the isolation of the 'Zone' also applies for the detector.
If all detectors in a 'Zone' have been isolated and the time limit for the isolation of
a detector elapses, the 'Zone' is displayed as switched on.
The 'Temporary ↑ switching-off' function can be used to set a time limit for
'Isolation'. The isolated part of the ↑ 'Site' is switched back on automatically after
the time period entered.
The figures below show exemplary operation sequences to temporarily ↑ switch off
'Section':
1. Select 'Main menu' > 'Element search'.
2. Select 'Start with category'.
Selecting element category
Zone
Area
↑ Section
Detector
RT control
Select 'Section' and confirm with <ok>.
κ
Enter address
↑ Section 1--------
Confirm with <ok>/Exit with <C>
Delete with <Cursor up>
Enter the address: e.g., 1. Confirm with <ok>.
κ
Switching off / Switching on
(1)
(2)
(3)
(4)
(5)
Operation
5
51 | 184
A6V10211076_i_en_--
2015-12-15