5
Switching off / Switching on
54 | 184
Building Technologies
Fire Safety
↑ Switching off ↑ 'RT Fire'
1. Select 'Main menu' > 'Topology'.
 The three partial topology trees are listed.
2. Select ↑ 'Control tree'.
 The 'Select element category' window is open.
3. Select the 'Alarmg.' list item.
 The 'Elements' window is open.
4. Select 'Alarmg. 2' and press 'Execute Commands' <softkey 2>.
 The 'Select command' window is open.
5.
WARNING! When the remote transmission Fire has been switched off, the
fire brigade cannot be called up in the event of fire! Select the 'RT FIRE
channels OFF' command and press <ok>.
 The command response confirms that the command has been executed.
 The 'RT Fire' is switched off.
 The LED 'Remote alarm Off' on the ↑ Person Machine Interface is illuminated.
LED statuses:
Off
Steady on with isolation
Flashing with fault
Example of ↑ switching off 'RT Fire' using 'Topology' main menu
item:
Topology
Exit with <C>
↑ Detection tree
Hardware tree
↑ Control tree
Function
On/Off
Select 'Control tree', continue with <ok>
κ
003 Elements
Evac gr
Alarmg.
Fire gr
Select 'Alarmg.', continue with <ok>
κ
(1)
(2)
(3)
Function
All
2
Evac control groups
2
Standard alarming controls
3
Elevator control
Lower
level
Access level 2.1
LED
test
Control tree