5.4.5 Switching off alarm activation
5.4.6 Switching off sabotage evaluation [DE]
Building Technologies
Fire Safety
WARNING! System parts that have been switched off make it impossible to
acquire and process alarms or faults! You can ↑ switch off the fire detection
installation alarm activation for specific elements with this function.
Faults such as the removal of a detector are nevertheless evaluated and displayed.
You can only run the 'Alarm evaluation OFF' command on the following elements:
'XC10 zone'
↑ 'Section'
'Automatic zone'
'Technical zone'
If a class 3 key safe (fire brigade key safe, 'FSD') forms part of the fire detection
installation and you want to open the housing of the control panel, you must
↑ switch off the sabotage evaluation.
NOTICE
Sabotage ALARM with police or security service
Costs due to unnecessary deployment.
●
In a site with 'FSD', switch off sabotage evaluation before you open the
housing of a control panel.
'Sabotage evaluation OFF'
ϖ Sabotage evaluation is switched on.
ϖ You have authorization for access level 3.
1. Select 'Main menu' > 'Topology'.
The three partial trees of the topology tree are indicated.
2. Select 'Hardware tree'.
One or more 'Stations' are displayed.
3. Select the 'Stations' to which 'FSD' is connected.
4. Press 'Lower level' <softkey>.
The elements of 'Stations' are displayed.
5. Select the element 'FSD'.
6. Press <Execute Commands>.
7. Select the 'Sabotage evaluation OFF' command.
Sabotage evaluation is switched off.
Operation
Switching off / Switching on
A6V10211076_i_en_--
5
57 | 184
2015-12-15