Switching Off Alarm Activation; Switching Off Sabotage Evaluation [De] - Siemens FC7xx Operation Manual

Fire control panel / fire terminal
Table of Contents

Advertisement

5.4.5 Switching off alarm activation

5.4.6 Switching off sabotage evaluation [DE]

Building Technologies
Fire Safety
WARNING! System parts that have been switched off make it impossible to
acquire and process alarms or faults! You can ↑ switch off the fire detection
installation alarm activation for specific elements with this function.
Faults such as the removal of a detector are nevertheless evaluated and displayed.
You can only run the 'Alarm evaluation OFF' command on the following elements:
'XC10 zone'
↑ 'Section'
'Automatic zone'
'Technical zone'
If a class 3 key safe (fire brigade key safe, 'FSD') forms part of the fire detection
installation and you want to open the housing of the control panel, you must
↑ switch off the sabotage evaluation.
NOTICE
Sabotage ALARM with police or security service
Costs due to unnecessary deployment.
In a site with 'FSD', switch off sabotage evaluation before you open the
housing of a control panel.
'Sabotage evaluation OFF'
ϖ Sabotage evaluation is switched on.
ϖ You have authorization for access level 3.
1. Select 'Main menu' > 'Topology'.
 The three partial trees of the topology tree are indicated.
2. Select 'Hardware tree'.
 One or more 'Stations' are displayed.
3. Select the 'Stations' to which 'FSD' is connected.
4. Press 'Lower level' <softkey>.
 The elements of 'Stations' are displayed.
5. Select the element 'FSD'.
6. Press <Execute Commands>.
7. Select the 'Sabotage evaluation OFF' command.
 Sabotage evaluation is switched off.
Operation
Switching off / Switching on
A6V10211076_i_en_--
5
57 | 184
2015-12-15