Switching Off / On The Remote Transmission Fire - Siemens FC7xx Operation Manual

Fire control panel / fire terminal
Table of Contents

Advertisement

5.4.3.1 Polling the isolation time
5.4.3.2 Expiry reminder for temporary switching-off

5.4.4 Switching off / on the remote transmission Fire

Building Technologies
Fire Safety
If a 'Zone' or 'Detector' level is temporarily switched off, you can poll the remaining
switching-off time at the ↑ 'Station'.
1. Select 'Main menu' > 'Message summary' > 'Isolations'.
2. Select the isolated element for which you wish to poll the remaining isolation
time.
3. Select 'Execute commands'.
 The 'Select command' window is displayed.
4. Select 'Show remaining off time' and confirm with <ok>.
 The remaining switching-off time is shown.
Execute command
Show remaining off time
Element is switched off
until 2013-11-16 13:49:49
An expiry reminder is displayed prior to the expiry of temporary isolation. You can
configure how long before a temporary isolation the reminder is displayed in
'Cerberus-Engineering-Tool'.
The expiry reminder must be configured in 'Cerberus-Engineering-Tool' > task
card 'Operation' > 'Global system configuration' > 'Global behaviour' > 'Details'
tab.
You will find more information about configuring the expiry reminder in document
'A6V10210424'. See chapter 'Applicable documents'.
WARNING
When the remote transmission Fire has been switched off, the fire brigade cannot
be called up in the event of fire!
Fire may spread unhindered.
Deploy staff to monitor the 'Site'.
You must switch the 'RT Fire' back on as soon as possible.
The 'RT Fire' is normally switched on and may only be switched off in particular
cases, e.g. for a function check of controls.
Operation
Switching off / Switching on
A6V10211076_i_en_--
5
53 | 184
2015-12-15