Mitsubishi Electric MELSEC FX3U Programming Manual page 946

Melsec fx series programmable logic controllers
Table of Contents

Advertisement

FX
/FX
/FX
Series Programmable Controllers
3G
3U
3UC
Programming Manual - Basic & Applied Instruction Edition
Error
PLC operation at
code
error occurrence
Operation error [M8067(D8067)]
0000
6701
6702
6703
6704
6705
6706
6707
6708
Continues
operation
6709
6710
6730
6732
6733
6734
6735
6736
6740
944
Contents of error
No error
• No jump destination (pointer) for CJ or CALL
instruction
• Label is undefined or out of P0 to P4095 due to
indexing
• Label P63 is executed in CALL instruction;
cannot be used in CALL instruction as P63 is for
jumping to END instruction.
CALL instruction nesting level is 6 or more
Interrupt nesting level is 3 or more
FOR-NEXT instruction nesting level is 6 or
more.
Operand of applied instruction is inapplicable
device.
Device number range or data value for operand of
applied instruction exceeds limit.
File register is accessed without parameter setting
of file register.
FROM/TO instruction error
Other (e.g. improper branching)
Mismatch among parameters
Incorrect sampling time (T
) (T
S
Incompatible input filter constant (α)
(α < 0 or 100 ≤ α)
Incompatible proportional gain (K
Incompatible integral time (T
Incompatible derivative gain (K
< 0 or 201 ≤ K
(K
)
D
D
Incompatible derivative time (T
) ≤ Scan time
Sampling time (T
S
This error occurs in the execution of operation.
Review the program, or check the contents of the
operands used in the applied instructions.
Even if the syntax or circuit design is correct, an
operation error may still occur.
For example:
"T500Z" itself is not an error. But if Z had a value of
100, the timer T600 would be attempted to be
accessed. This would cause an operation error
since there is no T600 device available.
This error occurs in the execution of operation.
• Review the program, or check the contents of
the operands used in the applied instructions.
• Verify that the specified buffer memories exist in
the equipment.
• Verify that the extension cables are correctly
connected.
This error occurs in the execution of operation.
Review the program, or check the contents of the
operands used in the applied instructions.
Even if the syntax or circuit design is correct, an
operation error may still occur.
For example:
"T500Z" itself is not an error. But if Z had a value of
100, the timer T600 would be attempted to be
accessed. This would cause an operation error
since there is no T600 device available.
This error occurs when the same device is used
within the source and destination in a shift
instruction, etc.
≤ 0)
S
<PID instruction is stopped.>
) (K
< 0)
P
P
This error occurs in the parameter setting value or
operation data executing PID instruction.
) (T
< 0)
I
I
Check the contents of the parameters.
)
D
) (T
< 0)
D
D
<Auto tuning is continued.>
The operation is continued in the condition
"sampling time (T
38 Error Check Method and Error Code List
38.4 Error Code List and Action
Action
) = cyclic time (scan time)".