Mitsubishi Electric MELSEC FX3U Programming Manual page 845

Melsec fx series programmable logic controllers
Table of Contents

Advertisement

FX
/FX
/FX
Series Programmable Controllers
3G
3U
3UC
Programming Manual - Basic & Applied Instruction Edition
5. Composition of branches and recombination
When a recombination line is directly connected to a branch line (not by way of a state relay as shown below),
it is recommended to provide a dummy state relay between the lines.
Create step ladder programs as shown below.
1) Selective recombination and selective branch
<SFC program>
20
X000
1
100
Dummy state
X003
3
50
2) Parallel recombination and parallel branch
<SFC program>
20
X000
1
101
Dummy state
S101
2
50
3) Selective recombination and parallel branch
<SFC program>
20
S102
1
102
Dummy state
X102
3
40
30
X001
TRAN
2
TRAN
X004
4
TRAN
TRAN
60
30
TRAN
TRAN
60
30
X001
TRAN
2
TRAN
TRAN
50
35 SFC Program and Step Ladder
<Step ladder>
STL
S20
X000
SET
S100
STL
S30
X001
SET
S100
STL
S100
X003
SET
S50
X004
SET
S60
<Step ladder>
STL
S20
STL
S30
X000
SET
S101
STL
S101
S101
SET
S50
SET
S60
<Step ladder>
STL
S20
X000
SET
S102
STL
S30
X001
SET
S102
STL
S102
S102
SET
S40
SET
S50
35.2 Step Ladder
31
32
<List program>
STL
S20
LD
X000
SET
S100
STL
S30
33
LD
X001
SET
S100
STL
S100
LD
X003
SET
S50
LD
X004
SET
S60
34
<List program>
35
STL
S20
STL
S30
LD
X000
SET
S101
STL
S101
LD
S101
SET
S50
36
SET
S60
37
<List program>
STL
S20
LD
X000
SET
S102
38
STL
S30
LD
X001
SET
S102
STL
S102
LD
S102
SET
S40
SET
S50
A
B
843

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec fx3ucMelsec fx3g

Table of Contents