Extension function (bi-directional transfer function)
By controlling the direction inverse flag M8024
two directions in one program.
X001
X000
FNC 15
BMOVP
M8001
Normally OFF
during operation
*1.
M8024 is cleared when the PLC mode is changed from RUN to STOP.
Caution
When specifying digits of bit devices, specify a same number of digits for
M8000
FNC 15
BMOV
*1
*1
BMOV
M8024
direction
inverse flag
S
D
n
D5
D10
K3
BMOV
*1
M8024
direction
inverse flag:
OFF
S
D
n
K1M0
K1Y000
K 2
Specify a same number
of digits.
(Example: K1)
9 Move and Compare – FNC 10 to FNC 19
for BMOV (FNC 15) instruction, data can be transferred in
BMOV direction
inverse flag
*1
: OFF
M8024
*1
M8024
: ON
S
M 0
Y000
M 1
Y001
M 2
Y002
M 3
Y003
M 4
Y004
M 5
Y005
M 6
Y006
M 7
Y007
9.6 FNC 15 – BMOV / Block Move
Transfer
S
,
D
direction
D5 → D10
D6 → D11
S
D
D7 → D12
D5 ← D10
D6 ← D11
S
D
D7 ← D12
and
.
D
n = 2