Error Check Method And Error Code List; States And Colors Of Leds Plc Operation Status; Power (Pow) Led [Lit, Flickering Or Unlit] - Mitsubishi Electric MELSEC FX3U Programming Manual

Melsec fx series programmable logic controllers
Table of Contents

Advertisement

FX
/FX
/FX
Series Programmable Controllers
3G
3U
3UC
Programming Manual - Basic & Applied Instruction Edition

38. Error Check Method and Error Code List

When an error occurs while the program is being executed, troubleshoot the cause of the error in accordance
with this chapter.
For error details, refer to the Data Communication Edition and the Hardware Edition of the PLC main unit.
38.1

States and Colors of LEDs PLC Operation Status

When an error has occurred, the PLC state can be checked using the LED status lights on the PLC.
FX
PLC
3U
FX
-32MT-LT(-2) PLC
3UC
RUN(Green)
BATT(Red)
ERROR(Red)
L.RUN(Green)
38.1.1 POWER (POW) LED [lit, flickering or unlit] [FX
LED status
Lit
Flickering
Unlit
932
POWER
(Green)
L.ERR
(Red)
PLC status
The voltage is correctly supplied to the power
terminal.
One of the following has occurred:
• The voltage or current is incorrectly
supplied to the power terminal.
• The wiring is incorrect.
• There is fault inside the PLC.
One of the following has occurred:
• The power is OFF.
• The voltage is incorrectly supplied to the
power terminal.
• There is a break in the power cable.
38.1 States and Colors of LEDs PLC Operation Status
FX
(D, DSS) PLC
3UC
POWER(Green)
RUN(Green)
BATT(Red)
ERROR(Red)
FX
PLC
3G
/FX
3G
The power supply is normal.
• Check the power supply voltage.
• Disconnect cables except the power cable, turn the PLC
power ON again, and check whether the status is
changed.
If the status is not improved, consult a Mitsubishi Electric
Distributor.
When the power is not OFF, check the power supply and
power line route.
When the power is correctly supplied, consult a Mitsubishi
Electric Distributor.
38 Error Check Method and Error Code List
POWER(Green)
RUN(Green)
BATT(Red)
ERROR(Red)
POWER
(Green)
RUN(Green)
ERROR(Red)
ALM (Red)
/FX
]
3U
3UC
Action

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec fx3ucMelsec fx3g