1. 16-bit operation (WBFM)
"n1" word units from
unit/block No. "m1". While transfering, "n1" is divided by "n2" so n1/n2 words (rounded up when there is a
remainder) are transferred per scan time.
Command
input
M8029
M8328
M8329
• When the instruction is finished normally, the instruction execution complete flag M8029 turns ON. When
the instruction is finished abnormally, the instruction execution abnormally complete flag M8329 turns ON.
• When the RBFM (FNC278) or WBFM (FNC279) instruction is executed in another step for the same unit
number, the instruction non-execution flag M8328 is set to ON, and execution of such an instruction is
paused.
When execution of the first target instruction is complete, the paused instruction resumes.
Related devices
→ For the flag use methods for instruction execution complete and instruction execution
Device
M8029
Instruction execution complete
M8328
Instruction non-execution
M8329
Instruction execution abnormally complete
Related instructions
Instruction
FROM(FNC 78)
TO(FNC 79)
RBFM(FNC278)
Errors
An operation error is caused in the following case; The error flag M8067 turns ON, and the error code is
stored in D8067.
• When the unit number "m1" does not exist (error code: K6708)
746
in the PLC are written to buffer memory (BFM) location # "m2" in special function
S
→ For the unit No., buffer memory (BFM) No., cautions, and program example,
FNC278
m1
m2
WBFM
M
M
M
Name
Read from a special function block
Write to a special function block
Divided BFM read
S
n1
n2
Instruction execution
complete
Instruction
non-execution
Instruction execution
abnormally complete
abnormally complete, refer to Subsection 6.5.2.
Turns ON when an instruction is finished normally.
Turns ON when RBFM (FNC278) or WBFM (FNC279)
instruction in another step is executed for a same unit number.
Turns ON when an instruction is finished abnormally.
Description
31 Data Transfer 3 – FNC275 to FNC279
31.2 FNC279 – WBFM / Divided BFM Write
refer to Subsection 31.1.1.
PLC
Unit No. "m1"
*1
Write
BFM#(m2)
S
+n1-1
BFM#(m2+n1-1)
S
*1 "n2" points are written in each
operation cycle. Writing is executed
in "n1/n2" transfers. ("n1/n2" is
rounded up if it is not an integer.)
Description