Mitsubishi Electric MELSEC FX3U Programming Manual page 405

Melsec fx series programmable logic controllers
Table of Contents

Advertisement

FX
/FX
/FX
Series Programmable Controllers
3G
3U
3UC
Programming Manual - Basic & Applied Instruction Edition
Output operation
Relay output type main unit
Special high speed output adapter
Transistor output type main unit
5. Others
1) Types of pulse output, positioning and other relevant instructions and their target output numbers
Classification
Pulse output
Positioning
High speed
processing
*1.
Y002 (pulse output destination) cannot be specified when the 14-point or 24-point type FX
connected.
*2.
The pulse output destination Y003 can be specified only when two special high speed output adapters
are connected to an FX
*3.
This function is supported only in FX
2) When using the same output relay (Y000 or Y001) in several instructions.
While a pulse output monitor (BUSY/READY) flag is ON, a pulse output or positioning instruction for the
same output relay cannot be executed.
While a pulse output monitor flag is ON, even after the instruction drive contact is set to OFF, a pulse
output or positioning instruction for the same output relay cannot be executed.
Before executing a pulse output or positioning instruction, wait until the pulse output monitor flag turns
OFF and one or more operation cycles pass.
Pulse output destination device
While instruction is active, associated output is ON. (LED is also ON.)
Use a special high speed adapter.
Set the output frequency to "200kHz" or less.
Set the output frequency to "100kHz" or less.
Instruction
PLSY(FNC 57)
Pulse Y output
PLSR(FNC 59)
Acceleration/deceleration setup
DSZR(FNC150)
DOG search zero return
*3
Interrupt positioning
DVIT(FNC151)
ZRN(FNC156)
Zero return
PLSV(FNC157)
Variable speed pulse output
DRVI(FNC158)
Drive to increment
DRVA(FNC159)
Drive to absolute
PWM(FNC 58)
Pulse width modulation
PLC.
3U
3U
Pulse output monitor flag
Y000
Y001
13 High Speed Processing – FNC 50 to FNC 59
13.10 FNC 59 – PLSR / Acceleration/Deceleration Setup
Output operation
Instruction name
/FX
PLCs.
3UC
M8340
M8350
Target output numbers
Y000,Y001
Y000,Y001
*1
*2
Y000,Y001,Y002
,Y003
*2
Y000,Y001,Y002,Y003
*1
*2
Y000,Y001,Y002
,Y003
*1
*2
Y000,Y001,Y002
,Y003
*1
*2
Y000,Y001,Y002
,Y003
*1
*2
Y000,Y001,Y002
,Y003
*1
*2
Y000,Y001,Y002
,Y003
PLC is
3G
403
11
12
13
14
15
16
17
18
19
20