Mitsubishi Electric MELSEC FX3U Programming Manual page 398

Melsec fx series programmable logic controllers
Table of Contents

Advertisement

FX
/FX
/FX
Series Programmable Controllers
3G
3U
3UC
Programming Manual - Basic & Applied Instruction Edition
Cautions
1. Setting the pulse width and period
Make sure that the pulse width
2. Pulse output
• Only the following outputs can be specified in
- When using special high speed output adapters
- When transistor outputs in the main unit are used: Y000, Y001, or Y002
*1.
High-speed output special adapters can be connected only to FX
When using the PWM (FNC 58) instruction with a relay output type FX
output adapter is required.
*2.
When specifying Y002 or Y003 on a special high speed output adapter, a second special high speed
output adapter is required.
*3.
Y002 is not available in 14-point and 24-point type FX
• The pulse output is controlled by interrupt processing not affected by the sequence program (operation
cycle).
• If the command input is set to OFF, the output from
• While a pulse output monitor (BUSY/READY) flag is ON, a pulse output or positioning instruction for the
same output relay cannot be executed.
While a pulse output monitor flag is ON even after the instruction drive contact is set to OFF, a pulse output
or positioning instruction for the same output relay cannot be executed.
Before executing a pulse output or positioning instruction, wait until the pulse output monitor flag turns OFF
and one or more operation cycles pass.
Pulse output destination device
396
and period
S
1
Pulse output monitor flag
Y000
Y001
Y002
Y003
13 High Speed Processing – FNC 50 to FNC 59
13.9 FNC 58 – PWM / Pulse Width Modulation
satisfy the relationship "
S
2
according to the system configuration.
D
*1
: Y000, Y001, Y002
3U
PLC.
3G
turns OFF.
D
M8340
M8350
M8360
M8370
".
S
S
1
2
*2
*2
, or Y003
*3
PLC.
PLC, a special high speed
3U