Dual High Level Milliamperes Inputs; Table 5-11 Set Up Wiring Procedure For Dual High Level Milliampere Inputs; Figure 5-9 Wiring Connections For Dual High Level Milliampere Inputs - Honeywell UDC3500 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

Input Calibration

5.4.8 Dual High Level Milliamperes Inputs

Refer to Figure 5-9 and wire the controller according to the procedure given in Table
5-11.

Table 5-11 Set Up Wiring Procedure for Dual High Level Milliampere Inputs

Step
Connect the copper leads from the calibrator to the input to be calibrated as shown in
1
Figure 5-9.
Place current source at zero before switching on.
2
3
Following calibration, turn off the current source prior to disconnecting it from the
instrument.
Milliampere
Source

Figure 5-9 Wiring Connections for Dual High Level Milliampere Inputs

290
250 ohms
250 ohms
250 ohms
250 ohms
+
250 ohms
_
Terminals for Input 1 are 35 (+) and 36 (-)
Terminals for Input 2 are 32 (+) and 33 (-)
Terminals for Input 3 are 29 (+) and 30 (-)
Terminals for Input 4 are 31 (+) and 33 (-)
Terminals for Input 5 are 28 (+) and 30 (-)
UDC3500 Universal Digital Controller Product Manual
Action
28+
Input 5
29+
Input 3
30-
31+
Input 4
32+
Input 2
33-
34R
35+
Input 1
36-
3/07