Viewing The Operating Parameters; Table 4-3 Lower Display Key Parameter Prompts - Honeywell UDC3500 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

Monitoring and Operating the Controller
Annunciator

4.5.2 Viewing the operating parameters

Press the
LOWER DISPLAY
4-3. The lower display will show only those parameters and their values that apply to
your specific model and configuration.

Table 4-3 Lower Display Key Parameter Prompts

Lower Display
OUT XX.X
SP XXXX
2SP XXXX
3SP XXXX
4SP XXXX
RSP XXXX
1IN XXXX
2IN XXXX
3IN XXXX
4IN XXXX
5IN XXXX
POS XX
CSP XXXX
DEV XXXX
PIDSET X
ET HR.MN
ØTR HR.MN
RAMPXXXM
SPn XXXX
PROGRAMX
198
2I—PV = Input 2 via a Digital Input activation
3I—PV = Input 3 via a Digital Input activation
Blinking indicates that the activity is being forced by a Digital Input.
key to scroll through the operating parameters listed in Table
OUTPUT—Output value is shown in percent with one decimal point for all output
types except Three Position Step Control (TPSC). For TPSC, when no slidewire is
connected, this display is an estimated motor position and is shown with no decimal
point. For Position Proportional Control, if the slidewire fails, then the instrument
automatically switches over to TPSC and the OUT display changes with it.
LOCAL SETPOINT #1—Also the current setpoint when using SP Ramp.
LOCAL SETPOINT #2
LOCAL SETPOINT #3
LOCAL SETPOINT #4
REMOTE SETPOINT
INPUT 1—Used only with combinational input algorithms.
INPUT 2
INPUT 3
INPUT 4
INPUT 5
SLIDEWIRE POSITION—Used only with TPSC applications that use a slidewire
input.
COMPUTER SETPOINT—When SP is in override.
DEVIATION—Maximum negative display is –999.9.
TUNING PARAMETER —where X is 1 to 4.
ELAPSED TIME—Time that has elapsed on the Timer in Hours.Minutes.
TIME REMAINING—Time remaining on the Timer in Hours.Minutes. The "Ø" is a
rotating clock face.
SETPOINT RAMP TIME—Time remaining in the Setpoint Ramp in minutes.
SETPOINT NOW—Current Setpoint when SP Rate is enabled. The SP XXXX
display shows the "target" or final setpoint value.
SETPOINT PROGRAM NUMBER— Set Point Programming display. X is the current
program number (1 to 4). When a Setpoint Program is initiated va the RUN/HOLD
key, the Setpoint Program Number can be incremented/decremented via the
keyboard. Digital Input Selections "PROG LO" and "PROG HI" override the keyboard
and force the Program selection per their status (open or closed). When running
linked programs, the Setpoint Program Number can be incremented/decremented
when in the "HOLD" mode.
UDC3500 Universal Digital Controller Product Manual
Indication
Description
3/07

Advertisement

Table of Contents
loading

Table of Contents