Second Current Output Calibration; Table 6-3 Set Up Wiring Procedure For The Second Current Output; Figure 6-2 Wiring Connections For Calibrating The Second Current Output - Honeywell UDC3500 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3500:
Table of Contents

Advertisement

Output Calibration

6.3 Second Current Output Calibration

Introduction
Calibrate the controller so that the output provides the proper amount of current over the
desired range. The controller can provide a current output range of from 0 mA to 21 mA.
The controller is usually calibrated at 4 mA for 0 % of output and 20 mA for 100 % of
output, but it may be calibrated for any other values between 0 mA and 21 mA. It is not
necessary to re-calibrate the controller in order to change from 4 to 20 mA operation over
to 0 to 20 mA operation, a simple configuration change is all that is required. See the CO
RANGE configuration for Second Current Output in Sub-section 3.22 for details.
Equipment Needed
You will need a calibrating device with whatever accuracy is required, capable of
measuring 0 to 20 mA.
Calibrator Connections
Refer to Figure 6-2 and wire the controller according to the procedure given in Table 6-3.

Table 6-3 Set Up Wiring Procedure for the Second Current Output

Step
Apply power and allow the controller to warm up 30 minutes before you calibrate.
1
2
Set LOCK in the Tuning Set Up group to NONE.
3
Tag and disconnect the field wiring, at the rear of the controller, from terminals 24 (+)
and 25 (–). See Figure 6-2.
4
Connect a milliammeter across these terminals.

Figure 6-2 Wiring Connections for Calibrating the Second Current Output

298
19
20
21
22
23
24
Curre nt
Output 2
25
26
27
UDC3500 Universal Digital Controller Product Manual
Action
Milliammeter
+
+
_
_
3/07

Advertisement

Table of Contents
loading

Table of Contents